Metric | Value |
---|
Summary of negative pressure decay timing, leakage volumes, and remaining margins.
High containment laboratories use cascading pressure differentials to make sure air always flows from clean corridors toward biohazardous suites. Engineers install exhaust fans, bubble-tight dampers, HEPA banks, and airlocks to maintain negative pressure even when people move through doorways. Yet if a storm or maintenance error kills the power to the exhaust trains, the room will inexorably equalize with the outside world. Facility teams often cite anecdotal statements such as āyou have about two minutes before the room goes positive.ā Those statements rarely account for the suiteās actual leakage area, the inertia of the exhaust blowers, or the way modern bubble-tight dampers slam shut. The coastdown calculator above gives biosafety officers a transparent, parameter-driven answer instead of handwaving.
The form prompts for the primary room volume and any connected anteroom. Both spaces contribute to the total compressible volume that delays equalization. The second fieldset captures leakageāthe sum of door gaps, utility penetrations, glove ports, and microscopic imperfections in the enclosure. Because leakage in high containment facilities is tiny, engineers usually express it as a conductance in liters per second per Pascal. The input representing leakage after damper closure allows users to mimic the fact that isolation dampers take a few seconds to close and that they reduce, but rarely eliminate, leakage. Finally, the fan coastdown fields recognize that large backward-curved exhaust wheels keep spinning for tens of seconds after a power trip. The tool therefore shows how the competition between inflow through leaks and outflow from coastdown determines the breathing room staff have before the suite loses its protective negative pressure.
The simulation treats the containment suite as a control volume with ideal gas behavior. Let be the combined volume in cubic meters, the absolute pressure inside, and the ambient pressure outside. The initial negative pressure setpoint is specified as (for example ā50 Pa). Leakage paths behave like a linear conductance, so the volumetric inflow driven by the pressure difference is , where is expressed in cubic meters per second per Pascal. Exhaust fans spinning down produce an outflow that decays exponentially with time constant . Combining the ideal gas law with mass conservation yields the differential equation
.
The calculator discretizes this first-order ordinary differential equation using one-second timesteps. Before the dampers close, the conductance uses the baseline value. After the delay, it multiplies the conductance by the percentage entered in the āLeakage after damper closureā field to reflect tighter sealing. The fan coastdown curve is modeled as , where is the residual exhaust flow at the moment of trip. By stepping forward in time and integrating the net inflow, the script reports how long it takes for the magnitude of the pressure difference to cross the user-defined safe limit.
Imagine a BSL-3 suite with a 140 m³ lab and a 20 m³ anteroom. The facility maintains a ā60 Pa offset during normal operation. Leakage testing revealed a conductance of 7 L/s per Pa, but when the bubble-tight dampers close the effective conductance plunges to 20% of that figure. The exhaust fans move 8 m³/min right before the power trip, and their coastdown follows a 30 second time constant. Running these numbers through the calculator shows that the suite stays below ā20 Pa for 184 secondsājust over three minutesābefore creeping upward. The integral of inflow indicates that 0.68 m³ of ambient air slips in during that time. The summary box also reports the minimum pressure achieved: because the fans continue to coast for several tens of seconds, the pressure actually dips to ā74 Pa before beginning its climb toward zero. The CSV timeline reveals that after five minutes, the room still holds ā11 Pa, which means the safe threshold was crossed only after the dampers had fully closed and the fanās inertia was spent.
Suppose maintenance crews replaced the door sweeps, cutting the baseline leakage conductance to 4 L/s per Pa. Rerunning the calculator with the improved seal extends the safe window to 312 secondsāmore than five minutes. Alternatively, if the damper actuators take 20 seconds to close because of a sluggish pneumatic system, the safe window shrinks dramatically: the pressure races toward zero within 90 seconds, because the leakage channels stay wide open while the fans spin down. Facilities can therefore use the tool to justify investments in faster actuators or redundant exhaust trains. The worked example underscores a crucial observation: most of the ābreathing roomā derives from either reducing leakage or harvesting a little more inertia from fans, not from simply increasing the room volume.
To highlight the planning leverage, the table compares three strategies applied to the sample suite described above.
Scenario | Leak conductance (L/s·Pa) | Damper delay (s) | Safe window (s) | Infiltration volume (m³) |
---|---|---|---|---|
Baseline | 7 ā 20% | 8 | 184 | 0.68 |
Faster dampers | 7 ā 20% | 3 | 237 | 0.54 |
Reduced leakage | 4 ā 20% | 8 | 312 | 0.61 |
Auxiliary flywheel fan | 7 ā 20% | 8 | 276 | 0.74 |
Accelerating the dampers trims infiltration during the critical first few seconds, buying almost a minute of additional safety. Tightening the envelope provides the longest benefit with only modest infiltration penalties. Installing a flywheel or battery-backed drive to keep the exhaust moving for longer also extends the window, though it may increase total infiltration because more outdoor air is sucked across cracks before the dampers seat. The calculator makes such trade-offs explicit so teams can coordinate mechanical upgrades with biosafety protocols.
The simulation assumes isothermal air and neglects density changes due to humidity or temperature swings. In real facilities, exhaust ductwork may still draft hot air upward, even without fans, slowing the decay. Conversely, if a fire suppression dump chills the room, the pressure may dip temporarily, causing the model to underpredict infiltration. The linear leakage model also ignores the fact that door cracks behave like orifices with flow proportional to the square root of pressure. For small differentials (below 50 Pa) the linear approximation is adequate, but for higher offsets you should adjust the conductance to match empirical tests. Additionally, the script treats the anteroom as perfectly mixed with the lab. In practice, airflow baffling may delay pressure equalization between spaces; you can approximate that by lowering the anteroom volume input.
Another limitation is that the model does not incorporate human activity. If someone opens the door during coastdown, the pressure collapses instantly. Similarly, if an emergency generator restarts the fans before the safe limit is crossed, the real recovery time will be shorter than predicted. Because the output includes a CSV timeline, facility managers can feed the data into more detailed building models that capture door events and smoke control interactions. Finally, while the tool quantifies pressure decay and infiltration volume, it does not track contaminant transport or aerosol dispersion. Once the room pressure crosses the safe threshold, the risk of exfiltration increases, but actual release depends on where pathogens reside and how quickly staff secure procedures. Use the calculator as a planning aid in tabletop exercises, and pair it with rigorous maintenance of seals, dampers, and emergency power.
Factor a non-negative matrix into two smaller non-negative matrices using multiplicative updates and view the reconstruction error.
Estimate the transient pressure spike caused by sudden changes in flow using the Joukowsky equation.
Compute atmospheric pressure at a given altitude using the barometric formula and explore how pressure decreases with height.