Daylight Factor (DF%) Calculator

Stephanie Ben-Joseph headshot Stephanie Ben-Joseph

Introduction: what daylight factor measures and why it survives

The daylight factor (DF) is the ratio of the illuminance at a point indoors to the simultaneous illuminance on an unobstructed horizontal plane outdoors, expressed as a percentage. Its defining trick is that it is a ratio under a CIE Standard Overcast Sky, so the absolute brightness of the day cancels out. Whether the sky delivers 5,000 lux or 20,000, a given room returns roughly the same DF, which is what makes it comparable between buildings, between design options, and between a measurement taken in March and one taken in November.

That robustness is also its limitation. Because the overcast sky is assumed uniform in azimuth, DF is blind to orientation: a north-facing and a south-facing window of identical size and obstruction return identical numbers. Annual climate-based metrics have largely replaced it for performance prediction, yet DF remains embedded in planning guidance, in BREEAM and Housing Quality Mark credits, and in the pocket of every surveyor with a lux meter, because it is the only daylight metric you can verify on site in under a minute.

This page runs both of the ways DF is used in practice. Measured mode takes two lux readings and returns the point daylight factor. Design mode implements the BRE and BS 8206-2 average daylight factor from window geometry, glazing transmittance, room surface area and reflectance — the calculation you need before the building exists and there is nothing to point a meter at.

How to use the daylight factor calculator in either mode

Pick a mode at the top of the form; the fields change to match.

Measured mode, from two lux readings

The tool only asks for two numbers, but the order you collect them in matters more than the arithmetic. Take the outdoor reading first with the sensor flat and the sky in full view, then get inside and take the indoor reading within a few seconds — daylight can shift 20 % between one passing cloud and the next, and a lagging outdoor number quietly inflates or deflates the whole ratio.

  1. Enter the outdoor illuminance in lux — the roof, terrace or open-ground reading with nothing shading the sensor.
  2. Enter the indoor illuminance in lux at your chosen workplane point, taken with the electric lights off so you are measuring daylight alone.
  3. Press Compute daylight factor. Re-run at two or three points across the room and compare, because one reading never speaks for the whole space.

Design mode, from window geometry

  1. Enter the room dimensions; the calculator derives the total internal surface area A from them, which is what the formula needs rather than the floor area alone.
  2. Enter the net glazed area — glass only, with the frame subtracted. On a typical domestic window the frame takes 20–30 % of the structural opening, so netting it out matters.
  3. Enter the angle of visible sky in degrees, measured in section from the centre of the window: 90° for a window with clear sky above the horizontal, less where a facing building, balcony or deep reveal cuts into the view. This is the single input that captures site context.
  4. Set glazing transmittance (about 0.9 for single clear glass, 0.7–0.8 for double, 0.6–0.7 for low-e triple), a maintenance factor for dirt (0.9 clean vertical glazing, down to 0.7 in dirty urban or industrial settings), and the average surface reflectance.
  5. Choose the room use so the result is checked against the right BS 8206-2 target.

Design mode also reports the net glazed area you would need to reach the target, which is usually the number you actually wanted.

Formulas: the point ratio and the BRE average daylight factor

The measured form is a plain ratio. With Ei the indoor illuminance at a point and Eo the simultaneous unobstructed outdoor horizontal illuminance, both in lux:

DF = Ei Eo × 100

The design-stage form is the Lynes expression codified in BRE Digest 309 and BS 8206-2, which estimates the average daylight factor across the whole working plane rather than the value at one point:

ADF= MTAwθ A(1R2)

where M is the maintenance factor for dirt on the glazing, T the diffuse visible transmittance of the glass, Aw the net glazed area in m2, θ the angle of visible sky in degrees, A the total area of every internal surface including the windows, and R the area-weighted average reflectance of those surfaces. Expressing θ in degrees is what makes the result come out directly as a percentage; there is no separate factor of 100.

For a rectangular room the surface area is worth writing out, because using floor area by mistake inflates the answer by a factor of four or more:

A=2WL+2H(W+L)

The 1R2 denominator is the interreflection term, and it bites hard. Raising average reflectance from 0.4 to 0.6 divides the denominator by 1.31, lifting ADF by 31 % for no change in glazing at all — which is why painting a room white is the cheapest daylighting intervention there is. Because ADF is strictly linear in Aw, the glazed area needed to hit a target follows by inversion:

Aw=ADFtargetA(1R2)MTθ

Worked examples: a desk reading and a living room on paper

Measured: an open-plan desk on a grey afternoon

Stand a colleague on the roof terrace with a lux meter facing the sky while you crouch at a desk two rows back from the window, both calling out numbers on a three-count so the readings line up:

DF = (360 ÷ 12,000) × 100 = 3.0 %. That lands squarely in the range most designers are happy to see on a workplane: enough diffuse light to read and work without reaching for the switch on a dull day, without the desk beside the glass becoming a glare trap. Before signing it off, walk the meter back toward the rear wall — desks near the core routinely drop below 1 % even when the front row measures a comfortable 3 %, and that falloff is the real story the single reading hides.

Design: a 4 m by 4 m living room with a facing terrace

Room 4.0 × 4.0 m with a 2.5 m ceiling, so A=2(16)+2(2.5)(8)=72 m2. One window with 2.0 m2 of net glass, double glazed at T=0.7, maintenance factor 0.9, and a building opposite that cuts the visible sky to θ=65°. Surfaces average R=0.5.

Numerator: 0.9 × 0.7 × 2.0 × 65 = 81.9. Denominator: 72 × (1 − 0.25) = 54.0. So ADF = 1.52 %, which just clears the BS 8206-2 living-room target of 1.5 % and falls well short of the 2 % a kitchen would need.

To reach 2 % the glass would have to grow to 2.0 × 54.0 ÷ (0.9 × 0.7 × 65) = 2.64 m2, a 32 % increase. Alternatively, lifting average reflectance from 0.5 to 0.65 — white walls and ceiling, pale floor — drops the denominator to 72 × 0.5775 = 41.6 and raises ADF to 1.97 % with no change to the window at all. Comparing those two routes is exactly what design mode is for.

Interpreting the number against published targets

BS 8206-2 sets minimum average daylight factors by room use, and BREEAM and the Housing Quality Mark share the same calculation procedure. CIBSE summarises the standard's headline positions: an average daylight factor should be at least 2 %, and where it reaches 5 % electric lighting is not normally needed during the daytime, provided uniformity is satisfactory.

Minimum average daylight factor by room use
RoomBS 8206-2 minimum ADFWhat it implies
Kitchen, utility2 %Task-heavy space; the most demanding domestic target
Living room, dining, study1.5 %Comfortable for reading and general occupation on a dull day
Bedroom1 %Lowest domestic target; occupation is largely outside daylight hours
Non-residential occupied spaces2 %The BREEAM and HQM credit threshold for adequately daylit spaces
Any space at 5 % or aboveElectric lighting not normally needed in daytime, if uniformity holds

For a point daylight factor from measured mode, read the same numbers as rough guidance rather than compliance: below 2 % the point is dim for daylight-only tasks, 2–5 % is generally useful, and above 5 % you are close enough to the glass that glare and solar gain deserve a look. DF is point-specific, so a single reading never describes a room; designers take readings on a grid to judge distribution and uniformity.

Daylight factor against the climate-based metrics

DF is easy to measure and compare, but it is not the only way to evaluate daylighting, and modern practice increasingly prefers metrics that know about orientation and weather:

BS 8206-2 itself was withdrawn in June 2019 and superseded by BS EN 17037, which introduced target illuminance methods. The average daylight factor nonetheless persists in planning practice, in BREEAM and HQM assessments, and in the AECB and Passivhaus workflows, which is why it is worth computing correctly.

Assumptions and limitations to read before quoting a number

Sources. The average daylight factor expression and its variable definitions follow BS 8206-2 and BRE Digest 309, as implemented in the AECB Daylight Standard, whose calculator states it is “based upon BS 8206-2, and informed by BRE BR209, BRE IP 15/88 and BRE Digest 309” and which tabulates the minimum daylight factors used above (kitchen and utility >2 %, living, dining and study >1.5 %, bedroom >1 %, non-residential occupied spaces >2 %). The “at least 2 %” and “5 % means electric lighting is not normally needed during the daytime” statements are quoted from BS 8206 in CIBSE, Daylighting and Compliance. The overcast-sky basis of the daylight factor definition is the CIE Standard Overcast Sky. BS 8206-2 was withdrawn in June 2019 and superseded by BS EN 17037, Daylight in Buildings. Last reviewed July 2026.

Daylight factor questions that come up on site

What counts as a good daylight factor?

BS 8206-2 sets minimum average daylight factors of 2 percent for kitchens and utility rooms, 1.5 percent for living rooms, dining rooms and studies, and 1 percent for bedrooms, with 2 percent also the BREEAM and Housing Quality Mark threshold for an adequately daylit non-residential space. CIBSE quotes the standard's position that an average daylight factor of at least 5 percent means electric lighting is not normally needed during the daytime, provided uniformity is satisfactory. For a single measured point rather than a room average, treat below 2 percent as dim, 2 to 5 percent as generally useful, and above 5 percent as bright enough to warrant a glare and solar gain check.

Why must the indoor and outdoor readings be taken at the same time?

Outdoor daylight changes quickly with passing cloud, often by 20 percent within seconds. Because the daylight factor is a ratio, a lag between the two readings distorts the percentage directly: an outdoor value captured a moment too early under a brighter patch of sky will understate the factor, and one captured under a darker patch will overstate it. Take both readings within a few seconds of each other, ideally with two people counting together.

What is the angle of visible sky and how do I measure it?

It is the angle, in degrees, subtended by the visible sky at the centre of the window, measured in a vertical section through the window. An unobstructed window with clear sky above the horizontal gives 90 degrees. A facing building, a balcony overhead, a deep reveal or a tree all cut into that view and reduce the angle. Measure it from a section drawing by drawing a line from the window centre to the top of the obstruction and reading the angle between that line and the line to the sky, or estimate it on site with a clinometer. It is the only input in the design formula that carries site context, so it is worth getting right.

Can I use this calculator on a sunny day?

You can compute the ratio, but it will not represent the traditional daylight factor. The definition assumes a CIE Standard Overcast Sky, and direct sun patches or fast-moving broken cloud make both readings jump around independently, producing values that are unstable and not comparable with anything else. If overcast conditions are unavailable, take many readings and note the sky condition alongside them, but do not quote the result as a compliance figure.

Why does painting the room raise the daylight factor so much?

Because the average daylight factor formula divides by one minus the square of the average surface reflectance, which is an interreflection term. Raising average reflectance from 0.4 to 0.6 shrinks that denominator by a factor of 1.31, lifting the daylight factor by 31 percent with no change to the glazing at all. White paint on walls and ceiling and a pale floor finish is generally the cheapest daylighting intervention available, and it improves uniformity at the back of the room rather than just the value near the window.

Should electric lights be on or off, and what units should I use?

Measure with the electric lighting off, or otherwise ensure the indoor reading reflects daylight alone, because any artificial contribution inflates the ratio. Use lux for both the indoor and the outdoor reading; since the daylight factor is a ratio the units cancel, so any consistent unit works, but lux is what every meter reports and what every standard is written in.

Daylight factor inputs

Measured mode gives the point daylight factor. Design mode gives the BS 8206-2 average daylight factor for the whole room.

Measure outdoors on a horizontal surface with an unobstructed view of the sky, at the same moment as the indoor reading.

Measure at the point of interest, usually the workplane about 0.8 m above the floor, with electric lights off.

Provide measurements to see the daylight factor.

Status messages will appear here.

Result against the published targets

In measured mode the bar places your point daylight factor against the dim, useful and bright bands. In design mode it plots average daylight factor against net glazed area, so you can read straight off how much glass the target needs.

Arcade Mini-Game: Daylight Factor Survey Run

Catch the survey habits that produce a defensible daylight factor and dodge the mistakes that quietly corrupt the ratio. Every bubble is a decision from the guidance above.

Score: 0 Timer: 30s Best: 0

Start the game, then use your pointer or arrow keys to catch sound survey habits and avoid the mistakes.