This calculator estimates the heat transfer area required for a simple heat exchanger using the classic UA–LMTD method. It is intended for single-phase heating or cooling where properties do not change dramatically with temperature. By combining mass flow rate, heat capacity, temperature change, overall heat-transfer coefficient, and the log-mean temperature difference (LMTD), the tool gives a first-pass approximation of the surface area needed to meet a specified heat duty.
The calculation is particularly useful in preliminary design, feasibility studies, and classroom examples. It helps you quickly see how required area changes with operating conditions such as flow rate, inlet and outlet temperatures, and the cleanliness or effectiveness of the exchanger (represented through the overall heat-transfer coefficient, U, and an LMTD correction factor, F).
The sizing procedure is based on two energy-balance relationships:
Q = m·cp·ΔT, where
Q = U · A · LMTD · F, where
Equating these two expressions for Q and solving for the required area gives
In code form this is often written as:
A = (m · cp · ΔT) / (U · LMTD · F)
The log-mean temperature difference accounts for the fact that the temperature difference between the hot and cold streams is not constant along the length of the exchanger. For simple counterflow or parallel-flow arrangements the LMTD is calculated from the four inlet and outlet temperatures:
Define the terminal temperature differences:
The LMTD is then
If ΔT1 and ΔT2 are very close to each other, the LMTD approaches that common value.
The form above asks for the key parameters needed to estimate the required area. All temperatures can be entered in degrees Celsius because only temperature differences appear in the equations. The tool internally uses differences in Kelvin, which are numerically identical to differences in Celsius.
After entering your data, submit the form to calculate:
The calculator returns the clean surface area required to transfer the specified heat duty under the given conditions. This area assumes that U and cp are already representative of your operating state and include any margin or fouling allowance you wish to apply.
Consider a simple counterflow exchanger where a hot process stream is cooled from 80 °C to 40 °C by a cold stream warmed from 20 °C to 60 °C. Assume:
Step 1: Heat duty
The hot stream is cooled by 40 K:
ΔT (hot) = 80 − 40 = 40 K
Heat duty is
Q = m · cp · ΔT = 1.0 · 4.0 · 40 = 160 kW
Step 2: LMTD
Terminal temperature differences:
Since ΔT1 = ΔT2, the LMTD equals this common value:
LMTD = 20 K
Step 3: Required area
Using A = Q / (U · LMTD · F) with F = 1:
A = 160 / (0.5 · 20 · 1.0) = 160 / 10 = 16 m²
The calculator will return an area of approximately 16 m² and LMTD ≈ 20 K for these conditions.
The following table illustrates how changing flow rate or temperature program affects required area, holding U and F constant at 0.5 kW/m²·K and 1.0, respectively. These numbers are approximate and correspond to the same calculation approach used in the tool.
| Flow (kg/s) | Hot In/Out (°C) | Cold In/Out (°C) | U (kW/m²·K) | Required Area (m²) |
|---|---|---|---|---|
| 1 | 80 / 40 | 20 / 60 | 0.5 | ≈ 16 |
| 2 | 80 / 40 | 20 / 60 | 0.5 | ≈ 32 |
| 2 | 90 / 40 | 30 / 60 | 0.5 | lower than 32 (higher LMTD) |
Comparing the first two rows shows that doubling the flow rate approximately doubles the required area when the temperature program and U are unchanged. The third row keeps the same flow but changes the temperature levels, which alters LMTD and therefore reduces the area compared to the second case.
This calculator is designed for clarity and speed rather than full engineering rigor. It relies on several simplifying assumptions:
Because of these limitations, treat the outputs as preliminary estimates. Use them to compare alternatives, perform quick what-if studies, or support educational exercises, but rely on comprehensive design methods, standards, or professional engineering judgment for final equipment specification.
When calculating LMTD from the four temperature points, certain edge cases can signal that the exchanger configuration is thermodynamically infeasible or outside the scope of this simple model. For example, if the cold outlet temperature exceeds the hot inlet temperature in a parallel-flow arrangement, or if either ΔT1 or ΔT2 becomes zero or negative, the LMTD expression can break down or produce non-physical values. In practice, such conditions indicate that the assumed flow arrangement or temperature targets need to be revisited. The calculator is primarily intended for cases where both terminal temperature differences are positive and of reasonable magnitude.
For detailed exchanger design, including proper selection of F for specific shell-and-tube layouts and checking feasibility of temperature programs, consult standard heat-transfer references or dedicated thermal design software.
The equations implemented here follow standard heat transfer and heat exchanger design practice as presented in common texts such as Incropera et al. Fundamentals of Heat and Mass Transfer and Kern, Process Heat Transfer. The content is intended for students, practicing engineers, and technicians who need a quick, transparent estimate of required heat transfer area before moving on to detailed design.
| Mass flow × cp | |
|---|---|
| Hot-side ΔT | |
| Cold-side ΔT | |
| Heat duty Q | |
| Log mean temperature difference | |
| Correction factor F | |
| Required surface area |